ÜRÜNLER

VTBF 10/20/30

vtbf-10-20-30-faz-toprak
Dahili Gerilim Transformatörü
Tip: VTBF
Tek Kutuplu
Sigortalı
Reçine Döküm
Faz-Toprak Arası
Indoor Voltage Transformer
Type: VTBF
Single Pole
With Fuse
Cast Resin
Phase to Earth

vtbf-10-20-30-faz-toprak-tech

TİP / TYPE 2VTBF 10 2VTBF 20 2VTBF 30 VTBF 30-6
İşletme gerilimi (mak.) / Operating voltage (max.) 7.2 kV-12 kV 17.5 kV-24 kV 36 kV 36 kV
Anma izolasyon test gerilimi (1 dk) / Rated power-frequency
withstand voltage (1 min.)
20 kV-28 kV 38 kV-50 kV 70 kV 70 kV
Anma darbe test gerilimi (1,2/50μs) / Rated impulse test voltage
(1,2/50μs) full wave
60 kV-75 kV 95 kV-125 kV 170 kV 170 kV
Anma frekansı / Rated frequency 50 Hz, 60 Hz
Anma primer gerilimi / Rated primary voltage 3.3 – 11/
√3 kV
15 – 22/√3
kV
30 – 36/√3
kV
30 – 36/√3
kV
Sekonder gerilimi / Secondary voltage 100/√3 V, 110/√3 V, 120/√3 V, 380/√3 V,
400/√3 V
Anma yükler doğruluk sınıfına göre (ölçü trafoları) / Rated burden
in class
0.2 10 VA 10 VA 20 VA 20 VA
0.5 60 VA 60 VA 90 VA 90 VA
1.0 100 VA 150 VA 150 VA 150 VA
Anma termik çıkışlı limiti / Rated thermal limiting output 400 VA / 4A 600 VA / 6A 800 VA
/ 6A
800 VA / 6A
Anma yükler doğruluk sınıfına göre (koruma trafolar›) / Rated
burden for protection purpose in class
3P 60 VA 60 VA 60 VA 60 VA
Anma gerilim faktör 8 saat / Rated voltage factor 8h 1.9 x Un
Sargının termik yük oranı toprak arıza tesbiti için / Thermal
burden rating of winding for earth-fault detection
4A 6A 6A 6A
Izolasyon Sınıfı / Insulation Class E
Çevre ısısı / Ambient temperature -5……….+35 °C
Rakım / Altitude 1000 m
Standart / Standard IEC, VDE, ANSI
Ağ›rl›k (yaklafl›k) / Weight (approx) 30 kg 56 kg 75 kg 55 kg